Terminating resistor
When connecting several appliances
via the RS485 interface, the terminat-
ing resistor must remain on the last
appliance.
Remove the terminating resistors
from the appliances in between.
External alarm
We recommend connecting the appliance
to an external alarm device.
There are various connection options at
thebackoftheappliance.
The appliance may only be connected
to an external alarm device by trained
personnel.
Floating alarm
output
Connectionto
RS485 interface
Note
The connectors are secured with
screws. To remove the connectors,
undo the left and right screws.
RS485 interface
Rx- / Tx-
Send/Receive data cable (negative
pole)
Rx+ / Tx+
Send/Receive data cable (positive
pole)
GND
Earth cable
N.O
Alarm output
Connectionforavisualwarninglightor
an acoustic alarm signal.
N.C
Operating light
Connectionforacontrollamptoindicate
that the appliance is in normal mode.
COM
External power supply unit
42V/8ADCmaximum
Minimumcurrent:150mA
Floating alarm output
These three contacts can be used to connect the appliance to
an optical or acoustic alarm device.
The connection is designed for a maximum of 42 V/8 A DC from
a safety extra-low voltage (SELV) source (minimum current:
150 mA).
Important
W h e n s u p p l y i n g m a i n s v o l t a g e t o t h e o a t i n g a l a r m c o n t a c t ,
the technical safety requirements of standard EN 60335
will not be satised.